Deions

Remote type

Manual type

Rated Voltage

11kV (covers up to 38kV)

Type Code

SGS-4A

SGS-6A

SGS-4M

SGS-6M

Rated Current

400A

630A

400A

630A

Rated Frequency

50 / 60Hz

Rated Short-time withstand Current

12.5kA(32.5kAp)/20kA(52kAp)/25kA(65Ap) – (r.m.s)/1sec

Rated Short Circuit Making Current

12.5kA(32.5kAp)/21kA(54.6kAp), 5Times (E3)

Current Switching

Capacity

Load-Current Switching(over E3)

400A/400Times

630A/400Times

400A/400Times

630A/400Times

20A/20

31.5A/20

20A/20

31.5A/20

Loop-Current Switching

400A/20Times

630A/20Times

400A/20Times

630A/20Times

Cable Charging Current Switching

25A/10Times

7.5A/10Times

Line Charging Current Switching

1.5A/10Times

Excitation Current Switching

14A/10Times

22A/10Times

14A/10Times

22A/10Times

Non-Voltage Switching

5,000Times (M2)

Rated Control Voltage

1Ø220VAC

/24VDC

1Ø220VAC

/24VDC

-

-

Rated Power FRequency Withstand

Dry

60kV / 1min

Wet

50kV / 10sec

Impulse Withstand Voltage (1.2 x 50)

150kV

SF6 Gas Filling Pressure

0.12 MPa,G (at 20ºC)

Working pressure of pressure relief device

0.4 ~ 0.6 MPa.G

Working pressure of low pressure interlocking device

0.05 ~0.09 MPa.G

IP Grade

Switch :IP67 Control unit :IP55 by IEC529

Pollution Level

Heavy and Very Heavy (Class 3 and 4) by IEC815

Environmental

Ambient temperature :-30 ~ 70ºC)

Altitude :below 1,000m (max.3,000m)

Applied Standards

IEC 60265-1,ANSI C37.90.1-2/62.45,ES 5925-0003

Model type

MT(Porcelain + Moldcone)

PT(Porcelain+Nema Termianal)

ST(Silicon+Nema Termianal)