Characteristics
-LED Motion Status Display Function
-RS-485 Communication Function (Option)
-Mov Fault Alarm Function (Option)
-Surge Counter Function (Option)
-Display replacement notice (Option)
- Ground verification (Option)


Technical Data (KSC IEC 61643-11)

Model

220S

480D

380Y

Electrical Properties

1PW

3P3W

3P4W

Maximum Continuous Usage Voltage           Uc

320V

550V

320V

Nominal discharge current (8/20uss)    In (L-N/N-PE)

20kA

20kA

20kA

Maximum discharge current (8/20uss) Imax (L-N/N-PE)

40kA

40kA

40kA

Voltage Protection Level                   Up

<2kV

<2kV

<2kV

                             Up(N-PE)

<2kV

-

<2kV

Response time                 tA (L-N/N-PE)

<25ns/100ns

<25ns

<25ns/100ns

Rated Short Circuit Current           ISCCR (L-N)

5kA

5kA

5kA

 

Mechanical Properties

Heat Protection

Yes

Temperature range

-40·C ~+80·C

Installation Method

4XM4 Bolt

Coverage protection rating

IP20

enclosure material

Steel 1.6mm

Show Replacement

RedED(ON)

Remote Monitoring Contact

Yes

Connection conductor section area

6mm²

 

SZK-040-XXX Installation

1. Preparation for installation
1) Disconnect the power of the breaker before installing the product.
2) Check the systematic voltage at the installation site.
3) Check the installation site system grounding method,and all grounding shall comply with the relevant regulations.

2. Installation method
1) Fix it near the target to protect SPD.
2) Cut the cable of the SPD to an appropriate length and process the terminal.
3) Connect the power terminal of the SPD to the load side of the breaker,and connect the ground terminal to the ground side.
4) After raising the breaker to supply power,check whether the power LED (Green) light is on or not on the fault LED (Red) light is not lit.

A SPD separator shall be installed on the load-side terminal of the three-phase four-wire branch breaker inside the panel or on the leaflet of the facility to be protected,and connected as shown in the run-off diagram above.

3. Precautions
1) When measuring voltage resistance and insulation resistance on a track,SPD must be separated from the track.(Performance of voltage resistance,insulation resistance,or other pressure tests with SPD connected causes failure)
2) Repairs or modifications of SPD arbitrarily can cause failure or malfunction.